For small to medium businesses, Schneider Electric offers this single phase Easy UPS designed for essential power protection needs even in the most unstable power conditions. This 2000VA double-conversion on-line 2U rackmount UPS provides pure sine wave power to handle a wide voltage range and inconsistent power conditions. The SRVS comes with IEC 320 C14 input and 4x IEC 320 C13 outlets. The On-Line UPS has a intelligent card slot for optional Network Management Card (AP9544, SRVSMB001, VGLS9901I) that enables network-based UPS monitoring and management. The UPS can connect to EcoStruxure IT or third-party centralized management platforms. The Built-in automatic and manual bypass provide seamless power to the load even in the event of an internal detected fault or error in UPS. The SRVS UPS is compatible with replacement battery cartridge APCRBCV201. The UPS and the built-in lead-acid battery has a 2-year warranty. Ideal for small data centers, manufacturing facilities, computer rooms, network storage devices, telecommunication, and healthcare IT.
Overview
Presentation |
For small to medium businesses, Easy UPS 1 Ph On-Line provides essential power protection for unstable power conditions, ensuring consistent and reliable connectivity at the most critical moments. |
Lead time |
Usually in Stock |
Batteries & Runtime
|
|
|
|
Battery type |
Lead-acid battery |
Battery voltage |
48 V |
Number of battery filled slots |
0 |
Number of battery free slots |
0 |
Battery recharge time |
4 h |
Battery life |
3…5 year(s) |
|
|
Battery charger power |
76 W rated |
General
Number of power module filled slots |
0 |
Number of power module free slots |
0 |
Redundant |
No |
Physical
Colour |
Black (RAL 7010) |
height |
8.6 cm |
Width |
43.8 cm |
Depth |
46.2 cm |
Net weight |
19.0 kg |
Mounting location |
Front |
Mounting preference |
Lower |
Mounting mode |
Rack-mounted |
USB compatible |
Yes |
Mounting position |
Horizontal |
Input
Input voltage limits |
110...285 V half load 160...280 V full load |
Network frequency |
40...70 Hz auto sensing |
Output
Maximum configurable power in VA |
2000 VA |
Maximum configurable power in W |
1600 W |
Output frequency |
50/60 Hz +/- 3 Hz sync to mains |
UPS type |
Double conversion online |
Wave type |
Sine wave |
Efficiency |
88 % (full load) |
bypass type |
Internal bypass (automatic and manual) |
Crest factor |
3 : 1 |
Conformance
product certifications |
CE UKCA |
Standards |
EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018 |
Environmental
Ambient air temperature for operation |
0…40 °C |
Relative humidity |
0…95 % non-condensing |
Operating altitude |
0...3000 m |
Ambient air temperature for storage |
-20…50 °C |
Storage Relative Humidity |
0…95 % non-condensing |
Storage altitude |
0…15000 m |
Acoustic level |
50 dBA |
IP degree of protection |
IP20 |
Communications & Management
Alarm |
Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
Free slots |
1 |
control panel |
Multifunction LCD status and control console |
Surge Protection and Filtering
Surge energy rate |
600 J |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
14.2 cm |
Package 1 Width |
55.1 cm |
Package 1 Length |
59.9 cm |
Package 1 Weight |
20.7 kg |